Tungsten copper contact
for high-voltage breaker is kind of oil-free switchgear that uses SF6 gas as arc
quenching medium and insulating medium. It has better performance in arc extinguish
and insulation than oil circuit breaker and has high requirement of
application, management, operation of SF6. So it main used for the voltage
level of 110kv.
It composed of porcelain
column structure: It also known as blocks, a plurality of identical unit
interrupters and pillar insulators can be used to form the circuit breakers of
different voltage levels. The circuit breaker consists of three independent
single-phase and one hydraulic, electrical control cabinet. Each phase consists
of two pillars of porcelain sets of four interrupters (fracture) in series. In each pillar
porcelain top of the unit is equipped with two unit interrupter, 120 ° angle
V-shaped arrangement, the two parallel capacitors are arranged horizontally.
Tank structure:
Using the advantages of box-type multi-oil circuit breaker, the circuit breaker
and the transformer together, compact structure, anti-seismic and anti-fouling
ability. It is generally three-phase split-type, single-phase from the base,
insulated porcelain casing, current transformers and single-break interrupter
with the shell composition. Each phase is equipped with a hydraulic mechanism
and a control cabinet which can be operated individually and can be operated in
three phases by means of electrical control.
Characteristic
1. As insulating
gas, SF6 has many advantages, is colorless, tasteless, non-toxic, non-flammable
inert gas and has performance in cooling arc. Especially cooling effect under
high arc temperature;
2. The chemical
effect of SF6 gas itself is very stable, and has a very high dielectric
strength;
3. Blocking
effect: give full play to the effect of air blowing arc, interrupter small
size, simple structure, breaking current, arc time is short, breaking capacitor
or inductor current without re-ignition, over-voltage;
4. Long
electrical life: 50kA full capacity of continuous breaking up to 19 times, the
cumulative breaking current up to 4200kA, maintenance cycle is long, suitable
for frequent operation;
5. Good sealing
performance: SF6 gas has lower water content, arc chamber, resistance and
pillar into separate air separation, on-site installation without opening,
after installation with automatic connection; installation easy maintenance,
and to prevent dirt and moisture Into the circuit breaker inside.